Ground Resistance | |
Ranges | 0.010 to 0.099Ω 0.10 to 0.99Ω 1.0 to 49.9Ω 50.0 to 99.5Ω 100 to 199Ω 200 to 395Ω 400 to 590Ω 600 to 880Ω 900 to 1200Ω |
Accuracy | 0.010 to 0.099Ω: ±(1% + 0.01Ω) 0.10 to 0.99Ω: ±(1% + 0.01Ω) 1.0 to 49.9Ω: ±(1% + 0.1Ω) 50.0 to 99.5Ω: ±(1.5% + 0.5Ω) 100 to 199Ω: ±(2% + 1Ω) 200 to 395Ω: ±(5% + 5Ω) 400 to 590Ω: ±(10% + 10Ω) 600 to 880: ±(20% + 20Ω) 900 to 1200Ω: ±(25% + 30Ω) |
Resolution | 0.001Ω 0.01Ω 0.1Ω 1Ω 0.5Ω 1Ω 5Ω 10Ω 20Ω 30Ω |
Current | |
Ranges | 0 to 9.95A 10 to 99mA 100 to 300mA 0.30 to 2.99A 3 to 9.9A 10 to 30A |
Accuracy | 0 to 9.95A: ±(2.5% + 1mA) 10 to 99mA: ±(2.5% + 5mA) 100 to 300mA: ±(2.5% + 10mA) 0.30 to 2.99A: ±(2.5% + 0.1A) 3 to 9.9A: ±(2.5% + 0.3A) 10 to 30A: ±(2.5% + 0.5A) |
Resolution | 0.5mA, 0.1mA, 1mA, 0.01A, 0.1A, 0.1A |
General Specifications | |
Range Selection | Autoranging |
Sampling Time | 0.5s |
Display | 9,999 count LCD display |
Backlit LCD | Yes |
User Selectable Alarms | Yes |
Display Hold | Yes |
Internal Memory | Yes up to 99 data points |
Autoshut off | Yes (after 5 mins) |
Power Supply | 4 "AA" Batteries |
Over Range Indicator | Yes |
Low Battery Indicator | Yes |
Jaw Opening | 1.26" (32mm) |
Overvoltage Category | CAT. III 300V |
Product Certifications | CE, RoHS |
Operating Temperature | 32 to 131°F (0 to 55°C) |
Operating Humidity | 10 to 90% |
Storage Temperature | -4 to 140°F (-20 to 60°C) |
Dimensions | 11.2 x 3.3 x 2.2" (285 x 85 x 56mm) |
Weight | 2.6lbs (1160g) |
This auto ranging earth resistance clamp meter measures ground resistance and leakage current. The R5700 has internal memory capable of storing up to 99 measurements, allow for a user to set alarm thresholds and features a double molded conductor clamp for added protection.
Features